某110kV避雷器开展带电检测,上次带电检测结果为:A相Ix=0.736mAIr=0.097mA;B相Ix=0.736mAIr=0.097mA;C相Ix=0.736mAIr=0.097mA,本次检测结果为:A相Ix=0.741mAIr=0.099mA;B相Ix=0.735mAIr=0.095mA;C相Ix=0.799mAIr=0.211mA(Ix为全电流有效值,Ir为阻性电流峰值),根据状态检修规程,该避雷器C相异常,应缩短试验周期并加强监测。
A、对
B、错